Wire Gauge Calculator: AWG Wire Size by Amps & Distance
This wire gauge calculator finds the minimum AWG for copper or aluminum from amps, one-way distance, voltage, and an allowed voltage-drop percent.
How to use
- Enter the load in amps, the one-way distance in feet, and the system voltage.
- Enter the allowed voltage-drop percent. 3% is a common branch-circuit target.
- Choose copper or aluminum, and DC, single-phase AC, or three-phase AC.
- Read the smallest AWG or kcmil size that stays within that drop, plus the drop that size produces.
Formula
Required circular mils = factor × K × I × L / VD. VD is system volts × allowed percent ÷ 100. The factor is 2 for DC and single-phase AC, and √3 (about 1.732) for three-phase. K is 12.9 for copper and 21.2 for aluminum. I is amps and L is one-way feet. The result is the smallest size in the table whose circular mils meet or exceed that number. Actual drop uses VD = factor × K × I × L / CM. The circular-mil table matches the voltage drop calculator.
Example. 20 A at 120 V, 100 ft one way, copper, single-phase, and a 3% allowed drop needs 14,333.3 circular mils. The smallest size is 8 AWG (16,510 cmil), which drops 3.125 V (2.60%).
Example. The same run in aluminum needs 6 AWG and drops 3.232 V (2.69%).
Example. 10 A at 12 V DC over 15 ft of copper, with 3% allowed, needs 8 AWG and drops 0.234 V (1.95%).
Voltage drop only
A bigger AWG number is a thinner wire. This page does not apply ampacity. In typical US residential copper wiring, 12 AWG is used on 20 A breakers and 14 AWG on 15 A, and a long run may need a larger size than that. Temperature ratings and local code still apply. Ask a licensed electrician before you buy wire.
Frequently asked questions
Does a bigger AWG number mean thicker wire?
No, the opposite. 10 AWG is thicker than 14 AWG.
What gauge for a 20 amp circuit?
In typical US residential copper wiring, 12 AWG is used on 20 A breakers and 14 AWG on 15 A. Long runs may need a larger size.
Why does distance matter?
Longer wire has more resistance, so voltage drop grows with length. Low-voltage DC systems are especially sensitive.
What voltage drop should I target?
3% is a common target for branch circuits; many 12 V DC builders aim for 3% or less on critical loads.
Is this code-compliant sizing?
It checks voltage drop only. Ampacity, temperature ratings, and local code also apply; consult a licensed electrician.
Related tools
- Building / DIYVoltage Drop CalculatorEstimate voltage drop and percent drop for a wire run by gauge, length, load, and material.
- Building / DIYWatts to Amps CalculatorConvert watts to amps for DC, single-phase AC, and three-phase circuits.
- Building / DIYBTU CalculatorEstimate AC or heater BTUs from room size and climate factors.
- Building / DIYTile CalculatorTile count and square footage from room size, tile size, grout, and waste.
- Building / DIYCarpet CalculatorTurn room dimensions into square yards of carpet and padding, with waste and cost.
- Building / DIYMulch CalculatorCubic yards and bag counts from bed area and mulch depth.