Voltage Drop Calculator for Copper and Aluminum Wire
This voltage drop calculator estimates voltage drop and percent drop for copper or aluminum wire from AWG gauge, one-way length, load amps, and system volts.
How to use
- Choose the AWG or kcmil size. Circular mils for that size come from the table on the form.
- Enter the one-way length in feet, the load in amps, and the system voltage.
- Choose single-phase or three-phase, and copper or aluminum.
- Read voltage drop, percent drop, and voltage at the load. A result above 3% is flagged.
Formula
Single-phase voltage drop is VD = 2 × K × I × L / CM. Three-phase voltage drop is VD = √3 × K × I × L / CM, where √3 is about 1.732. K is 12.9 for copper and 21.2 for aluminum. I is load amps, L is one-way length in feet, and CM is circular mils. Percent drop is VD ÷ system volts × 100. Voltage at the load is system volts − VD.
Example. 12 AWG copper (6,530 circular mils), 100 ft one way, 20 A, 120 V, single-phase: VD = 2 × 12.9 × 20 × 100 / 6,530 = 7.902 V, which is 6.58% and leaves 112.098 V at the load.
Example. The same run on three-phase uses √3 instead of 2, so the drop is 6.843 V (5.70%).
Example. The same single-phase run in aluminum (K = 21.2) drops 12.986 V (10.82%).
Branch-circuit guideline
NEC informational notes suggest no more than 3% voltage drop on a branch circuit and 5% total for the feeder plus the branch. Those notes are not a sizing method by themselves. Conductor size also depends on ampacity, temperature, and how the wire is installed. This is an estimate only. Follow local code and have a licensed electrician design critical circuits.
Frequently asked questions
What is the voltage drop formula?
For single-phase: VD = 2 x K x I x L / CM, where K is about 12.9 for copper (21.2 for aluminum), I is amps, L is one-way length in feet, and CM is the wire's circular mils.
How much voltage drop is acceptable?
NEC informational notes suggest no more than 3% on a branch circuit and 5% total for feeder plus branch.
How do I reduce voltage drop?
Use a larger wire (smaller AWG number), shorten the run, raise the voltage, or reduce the load.
Is aluminum wire worse?
Aluminum has higher resistance than copper, so it needs a larger size for the same drop.
Is this a substitute for an electrician?
No. It is an estimate; follow local code and have a licensed electrician design critical circuits.
Related tools
- Building / DIYWatts to Amps CalculatorConvert watts to amps for DC, single-phase AC, and three-phase circuits.
- Building / DIYSquare Footage CalculatorLength × width for rooms in feet, inches, or meters, plus sq ft ↔ sq m.
- Building / DIYMillimeters to Inches ConverterConvert mm ↔ inches with exact 25.4 factor and fraction readout.
- Building / DIYConcrete CalculatorCubic yards, cubic feet, and 60- or 80-lb bag counts for slabs, footings, and columns.
- SchoolPercentage CalculatorFind X% of Y, what percent one number is of another, percent change, and an optional percent table.
- SchoolRatio CalculatorSimplify ratios, scale A:B parts, and find missing values.