Watts to Amps Calculator (DC, AC, 3-Phase)
This watts to amps calculator converts watts to current for DC, single-phase AC, and three-phase circuits using volts and power factor.
How to use
- Choose DC, single-phase AC, or three-phase (line-to-line).
- Enter watts and volts. For three-phase, volts are line-to-line.
- For AC, enter the power factor. Use 1.0 for a resistive load such as a heater. DC does not use power factor.
- Read the current in amps, or use a 120 V or 240 V household example. Clear empties the fields.
Formula
DC current is I = P / V. Single-phase AC is I = P / (PF × V). Three-phase line-to-line current is I = P / (√3 × PF × Vll), where √3 is about 1.732. Power factor is greater than 0 and at most 1, and it is not used for DC. Volts must be greater than 0.
Example. A 1,200 W load on 120 V DC draws 1,200 / 120 = 10 A. On single-phase AC with a power factor of 0.8, the same load draws 1,200 / (0.8 × 120) = 12.5 A.
Example. 10,000 W on a 208 V three-phase circuit at power factor 1 draws 10,000 / (√3 × 208) ≈ 27.757 A.
Example. 15 A × 120 V = 1,800 W. The usual 80% continuous-load rule is about 1,440 W. This page does not size a breaker or a wire.
Breaker and wire sizing
The amps here are the current a load draws at the volts and power factor you enter. They are not a breaker size or a wire size. Continuous loads are often limited to 80% of the breaker rating, and conductor size also depends on the electrical code, temperature, and how the wire is installed. Ask a licensed electrician before you choose a breaker or conductor.
Frequently asked questions
How do I convert watts to amps?
For DC, amps = watts / volts. A 1,200 W load on 120 V draws 10 A.
What about AC circuits?
Single-phase AC: amps = watts / (power factor × volts). Three-phase: amps = watts / (1.732 × power factor × line-to-line volts).
How many watts can a 15 amp circuit handle?
15 A × 120 V = 1,800 W. For continuous loads, the usual 80% rule limits you to about 1,440 W.
What is power factor?
The ratio of real power to apparent power. Resistive loads like heaters are close to 1.0; motors are often lower.
Can I use this to size a breaker or wire?
Use it as a starting point only. Breaker and conductor sizing follows the electrical code; ask a licensed electrician.
Related tools
- Building / DIYBrick CalculatorBricks and mortar for a wall from its size, openings, brick size, and joints.
- Building / DIYMillimeters to Inches ConverterConvert mm ↔ inches with exact 25.4 factor and fraction readout.
- Building / DIYSquare Footage CalculatorLength × width for rooms in feet, inches, or meters, plus sq ft ↔ sq m.
- Building / DIYConcrete CalculatorCubic yards, cubic feet, and 60- or 80-lb bag counts for slabs, footings, and columns.
- SchoolPercentage CalculatorFind X% of Y, what percent one number is of another, percent change, and an optional percent table.
- SchoolRatio CalculatorSimplify ratios, scale A:B parts, and find missing values.